2/14/2018 4:37 PM 
 
 
 
 
UST Compliance Inspection Checklist 
Connecticut Department of Energy and Environmental Protection 
Storage Tank and PCB Enforcement Unit 
79 Elm Street, Hartford, CT 06106 
860-424-3374 
 
 
GENERAL:  
Inspection Date: 2/14/2018 
Site ID: 
152-3068 
Inspector 
Gary Bellmar 
Site Name 
SOUTHWEST SCHOOL 
Reason 
Compliance 
Site Address  
DANIELS AVE. Waterford, CT 06385 
Inspection  
Type 
Full Inspection 
 
Contacts 
Contact Type 
Contact Information 
Owner 
TOWN OF WATERFORD, 15 ROPE FERRY RD WATERFORD, CT 06385, Phone: (203) 444-
5801- 
Registrant 
TOWN OF WATERFORD, 15 ROPE FERRY RD WATERFORD, CT 06385 
 
 
 
 
Tank ID: SW1R1 - Currently In Use (10000 gallons) – Installed: 11/1/1988 
Construction 
Coated & Cathodically Protected Steel 
(sti-P3) 
Life Expectancy 
30 years 
Construction Notes 
 
Tank Options 
 
Corrosion Protection Type: Galvanic (Sacrificial Anode) 
Impressed Current System  
  
Structure to soil voltage  
 
Compartment: a - Heating Oil(on-site consumption) (10000 gallons) 
Spill Prevention 
Spill Containment 
Overfill Prevention 
Ball Float Device 
Product Notes 
 
Spill Prevention Note 
 
Release Detection 
No release detection required 
 
 
Piping – Installed: 11/1/1988  
Construction 
Other (Specify) 
Corrosion Protection Type 
Not Required 
Construction Notes 
Piping material: B Piping 
Installed: 11/88 
Piping Options 
Single Walled, Containment 
Sumps @ Tanks, Metallic 
fittings isolated from soil and 
water 
Piping Release Detection 
Pump Type 
American Suction (Check 
Valve is at Tank) 
Line Leak Detector 
 
Primary Method 
Precision LTT Every 3 years 
 
Tank ID: SW2R1 - Currently In Use (2000 gallons) – Installed: 11/1/1988 
Construction 
Coated & Cathodically Protected Steel 
(sti-P3) 
Life Expectancy 
30 years 
Construction Notes 
 
Tank Options 
Double Walled 
Corrosion Protection Type: Galvanic (Sacrificial Anode) 
Impressed Current System  
  
Structure to soil voltage  
 
Compartment: a - Heating Oil(on-site consumption) (2000 gallons) 
Spill Prevention 
Spill Containment 
Overfill Prevention 
Ball Float Device 
Product Notes 
 
Spill Prevention Note 
 
Release Detection 
No release detection required 
 
 
Piping – Installed: 11/1/1988  

Page 2 of 2 
2/14/2018 4:37 PM 
Construction 
Other (Specify) 
Corrosion Protection Type 
Not Required 
Construction Notes 
Piping material: B Piping 
Installed: 11/88 
Piping Options 
Single Walled, Containment 
Sumps @ Tanks, Metallic 
fittings isolated from soil and 
water 
Piping Release Detection 
Pump Type 
American Suction (Check 
Valve is at Tank) 
Line Leak Detector 
 
Primary Method 
Precision LTT Every 3 years 
 
 
 
 
 
Narrative Comments  
02/14/2018 Inspector: Gary Bellmar - Site has two steel UST’s , one 10K and one 2K. Both UST’s need to have annual 
cathodic protection testing done. Notice of Violation issued. Annual Tank Notification needs to be updated on-line via EZFile 
to CT DEEP. Written Warning issued.  
 
Potential Violations  
Regulation: CT state regulation (d)-1(d) 
Violation Reason: A review of DEP records indicates that we do not have a registration form with current information. 
Required Action: Please provide a completed registration through EZ-File for the facility and all unregistered UST systems. 
 
Regulation: CT state regulation (d)-1(e)(1)(E) 
Violation Reason: Cathodic protection systems require annual testing to ensure that a structure to soil test voltage 
reading of at least minus 0.85 volts is maintained. 
Required Action: The UST system owner or operator must have the requisite CP test performed on the tank and/or piping.  
Applies To: TANK SW1R1 (Containing Heating Oil(on-site consumption) with Capacity of 10000 gallons) 
Applies To: TANK SW2R1 (Containing Heating Oil(on-site consumption) with Capacity of 2000 gallons) 
 
 
 
Inspector Signature 
 
Recipient Signature 
 
TOWN OF WATERFORD 
Recipient Printed Name 
 
Facility Owner 
Position/Title