Addendum _ 2 - RZ 23-122
document center
| Pages | 2 |
|---|---|
| File Size | 0.7 MB |
| Folder | Departments/Purchasing |
| OCR Status | Searchable (OCR processed) |
| Source URL | Original |
Document Preview
Full Text (OCR Extracted)
Legnos and Cramer, Inc. is now RZ Design Associates, Inc. Serving the Community Since 1952 May 22, 2023 ADDENDUM No. 2 To become part of the Contract for the project: BID# 23-122 TOWN OF WATERFORD PUBLIC SAFETY FACILITY AND POLICE STATION BOILER ROOM UPGRADES WATERFORD, CT QUESTIONS AND ANSWERS: Q: Where is the intended location of the temporary water heater? What are the electrical specs? A: The temporary electric water heater shall be located in the boiler room. A standard 40 gallon, 4500 watt, 208/1 volt water heater is to be provided. Contractor to provide 30A, 2P circuit breaker and wiring from boiler room panel. DRAWING M1.1 PUBLIC SAFETY FACILITY MECHANICAL PARTIAL PLANS: 1. Refer to attached sketch MSK-1 for boiler condensate pipe route. DRAWING M2.1 POLICE STATION MECHANICAL PARTIAL PLANS: 1. Detail 1/M2.1: Remove existing disconnect switches associated with the existing pumps. 2. Detail 2/M2.1: Install new fused disconnect switches furnished by pump manufacturer. 3. Detail 3/M2.1 Pump Schedule: ADD “Note #4: Provide optional fused disconnect switch for each pump.”. Attachments: Sketch MSK-1 +++++ END OF ADDENDUM No. 2 +++++ 750 Old Main Street – Suite 202 Rocky Hill, CT 06067 Phone: (860) 436-4336 • Fax: (860) 436-4450 www.rzdesignassociates.com